DC2800
Intelligent Multifunctional Meters DC2800-A
1. Summarize

Mounted multi-rate watt-hour meter is a kind of intelligent meter with functions of measure, display, communication, energy pulse output and programmable, up to 2 sets of 12-hour sections with 4 kinds of rates. Standard RS-485 communication interface, in line with Modbus-RTU communication protocol. With blue backlit LCD display, the installation structure is screen loaded mode, they can be widely used for energy metering, management and evaluation, application in substation, power distribution room, intelligent building and enterprise internal etc.

The products meet the national standard GB/T 17883-1999 and GB/T 15284-2002. Products comply with GB/T22264. 1-2008, GB/T13978-2008

2.     Typical Product Pictures

3.     Models and Meaning of Products

4.     Products Models

Model

Product function

DC2800-A

DC2800-B

Real-time measurement

Three-phase voltage

Three-phase current

Active power

Reactive power

Apparent power

Power factor

Frequency

Electric energy metering

Active electric energy

Reactive electric energy

Bi-directional metering

Harmonic wave

2-31 times of odd harmonic component

Real-time clock

Year, Month, Date, Hour, Minute, Second

Electric energy pulse

Passive stem node

2

2

Analog output

AO (DC4-20mA)

4

2

On-off output

(Relay output)

DO/RO (AC400V/0.1A,

or AC250V/5A)

4

2

On-off input

DI (Passive stem node)

4

2

Communication interface

RS485, Modbus-RTU

Display mode

LCD

LCD

Panel size (mm)

120x120

96x96

Hole size (mm)

111x111

91x91

Installation mode

Panel Mounting

Panel Mounting

Remark:

1)     ” means the model has the function.

2)     “ - “ means the model doesn’t have such function.

3)     The number means channel, for example: 2 means the model has the function with 2 channels.

5.     Technical Specifications

Description

Parameters

Precision grade

Electric capacity metering: active electric energy: 0.5 class, reactive electric energy grade:1.0, transmission output grade 0.5

Display mode

LCD screen display

Input signal

Measurement network

Three-phase four-wire V34/Three-phase three-wire V33

Voltage

Rated voltage

AC100V, AC400V

Excess load

Continuance: 1.2 times; Instantaneous: 2 times (10s)

Power consumption

0.6VA (each phase)

Impedance

200kΩ

Current

Rated current

AC5A / AC1A

Excess load

Continuance: 1.2 times; Instantaneous: 10 times (5s)

Power consumption

0.4VA (each phase)

Impedance

20mΩ

Frequency

45-65Hz ( -0.01Hz)

Harmonic wave

The voltage and current harmonic wave content and 2-31 times of odd harmonic component

Electric energy

Bi-directional Active/Reactive electric energy metering

Power supply

Working scope

AC/DC 85-264V

Power consumption

5VA

Function modules

Electric energy pulse

Passive optical coupler collector output

Communication interface

1-way RS485 communication interface, Modbus-RTU Protocol

On-off input

Passive stem node

On-off output

Excess alarm or remote relay output capacity AC5A/250V, AC/DC/0.1A /400V

Transmission output

0-20mA/4-20mA/0-5V/1-5V transmission output, programmable to setting transmission items and relative output data.

Security

Insulation resistance

100MΩ

Resist pressure

Input voltage1kV,  Input and output2kV, Power supply and output2kV

Work environment

Temperature

-10℃~55

Relative humidity

93RH

Altitude

Non-corrosive gas forum, Altitude 2500m

storage environment

Temperature

-20℃~75

Relative humidity

93RH

6.     Outline Dimension

DC2800-A

DC2800-B

7.     Typical Functions Terminal Numbering

8.     Typical Signal Input Wiring Diagram

DC2800-A

DC2800-B

Note: the above diagram is only for reference, the actual parameters in the factory shall prevail.

Wiring Instruction:

l   Input voltage cannot exceed rated input voltage (100V or 400V), otherwise should consider using PT, in order to make maintenance easily, advice to use connector bar.

l   Standard rated input current is 5A or 1A, if in the situation of more than 5A, should use exterior CT. If using CT with other meters, wiring method should be series connection, before removing the wire of input current, make sure that cut off CT one circuit or Short sub-secondary circuit in advance, in order to make maintenance easily, advice to use connector bar.

l   Make sure input voltage is correspond with input current, phase no. consistent, directions are consistent, otherwise the value and the symbol of power and electric energy will be wrong.

l   The meter can work in three-phase four-wire or three-phase three-wire mode, the users should select the appropriate wiring way based on the site situation. Usually under the situation without center line, use three-phase three-wire mode, while three-phase four-wire mode under the situation of center line. Please pay attention that onsite wiring mode must be consistent with the wiring default setting of the meter, otherwise the data of measured by meters will be incorrect.

9.     Ordering Example

l   Model: DC2800-B

l   Signal Input: AC220V, AC200A/5A

l   Wire Connection Mode: three-phase three-wire (2CT, 2PT)

l   Transmission Output: 4-ways

Transmission 1: DC4-20mA corresponds to Uab

Transmission 2: DC4-20mA corresponds to Ia

Transmission 3: DC4-20mA corresponds to Psum

Transmission 4: DC4-20mA corresponds to Qsum

l   Communication: RS485

l   Other: other factory pre-sets (if no indication when ordering, ex-factory products will be delivered in accordance with the default setting).