PRODUCT |
|
Changzhou Dacan Electronic Co., Ltd Mob: +86(0)13915077376 Tel: +86-519-85606622 Fax: +86-519-85607968 E_mail: sales@czdacan.com Web: www.oudz.cn |
1. Summarize
The intelligent temperature and humidity controller adopts various high and new technologies such as microprocessor technology, transducer technology, communication technology, etc. to carry out measurement, integrated control and alarming, etc. on the monitored environment. Taking micro-controller unit as the core of controlling, this product is of digital display, key-pressing setting functions and mainly used for temperature, humidity and condensation protection of such equipment as power switch cabinet, terminal box, transformer, cabinet substation, etc., so as to guarantee the safe and reliable running of power equipment.
2. Typical Product Pictures
DC2613
3. Models and Meaning of Products
4. Products Models
Model Product function |
DC2613 |
Temperature sensor |
2 |
Humidity sensor |
2 |
Heating type |
√ |
Cooling type |
√ |
Wire break alarm output |
√ |
Display mode |
Digital LED |
Panel size (mm) |
72x72 |
Hole size (mm) |
67x67 |
Installation mode |
Panel mounting |
Remark: 1) “√” means the model has the function. 2) “ - “ means the model doesn’t have such function. 3) The number means ways, for example: 2 means the model has the function with 2 ways. |
5. Technical Specifications
Description |
Parameters |
|
Measuring range |
Temperature |
-40℃ ~ 125℃ |
Relative humidity |
1% RH ~ 99% RH |
|
Measurement precision |
Temperature |
1℃ |
Relative humidity |
2% RH |
|
Factory default values |
Temperature 1 (heating type) |
≤5 ℃ when the heat relay closure, |
≥13 ℃ when the heat relay reset |
||
Temperature 2 (cooling type) |
≥40 ℃ when the heat relay closure |
|
≤25 ℃ when the fan relay reset |
||
Relative humidity |
≥85% RH when the heat relay closure |
|
≤75% RH relays reset |
||
Power Supply |
Rated input |
AC/DC85~265V |
Power consumption |
≤3W |
|
Relay contacts capacity |
220V AC, 5A |
|
Security |
Insulation resistance |
≥100MΩ |
Resist pressure |
Input-output: 2kV/1min |
|
Work environment |
Temperature |
-10℃~55℃ |
Relative humidity |
≤93%RH |
|
Altitude |
Non-corrosive gas forum, Altitude ≤2500m |
|
Storage environment |
Temperature |
-20℃~75℃ |
Relative humidity |
≤93%RH |
|
MTBF |
≥50000H |
6. Outline Dimension
7. Wiring Diagram
Note: the above diagram is only for reference, the actual parameters in the factory shall prevail.