Digital power factor meter are applied in the electric power grid, automatic control systems, the main usage is to measure power factor in the electric power grid, in accordance with the additional functions, the meters can be divided into 3 series digital display meters: X, K, S series.
X Series intelligent digital display power factor meters are through AC sampling directly, and using software to measure the power factor, they are digital electric capacity meters that display directly by the meter head digital diode (LED) or liquid crystal (LCD).
K Series intelligent digital display power factor meters based on the X-series, have an increase of one way analog transmission output (4-20mA, etc.) and one way RS-485 communication interface output(using the Modbus-RTU protocol), in order to facilitate digital display meters in the group networking.
S series digital alarm monitoring control meters are based on the X-series, to increase four-way switch value input measurement function and two-way relay alarm output function (to achieve “the remote control function”). Specific technical standard please refer to general specification of digital display meters.
The Products meet the standard of GB/T22264.1-2008, GB/T 13978-2008.
2. Typical Product Pictures
3. Models and Meaning of Products
4. Products Models
Model Product function |
DC284H-2X1 |
DC284H-9X1 |
DC284H-1X1 |
|
Real-time measurement |
Three-phase voltage |
- |
- |
- |
Three-phase current |
- |
- |
- |
|
Active power |
- |
- |
- |
|
Reactive power |
- |
- |
- |
|
Power factor |
√ |
√ |
√ |
|
Frequency |
- |
- |
- |
|
Analog output |
AO (DC4-20mA) |
- |
- |
- |
Relay output |
DO (AC250V/5A , Remote/Alarm |
- |
- |
- |
On-off input |
DI (Passive stem node) |
- |
- |
- |
Communication interface |
RS485, Modbus-RTU |
- |
- |
- |
Display mode |
One-line LED |
|||
Panel size (mm) |
120x120 |
96x96 |
158x78 |
|
Hole size (mm) |
111x111 |
91x91 |
151x71 |
|
Installation mode |
Panel Mounting |
|||
Remark: 1) “√” means the model has the function. 2) “ - “ means the model doesn’t have such function. 3) The number means channel, for example: 2 means the model has the function with 2 channels. |
5. Technical Specifications
Parameters |
|||
Precision grade |
Electric capacity metering: active electric energy: 0.5 class, reactive electric energy grade:1.0, transmission output grade 0.5 |
||
Display mode |
LED display |
||
Input signal |
Measurement network |
Three-phase four-wire V34/Three-phase three-wire V33 |
|
Voltage |
Rated voltage |
AC100V, AC400V |
|
Excess load |
Continuance: 1.2 times; Instantaneous: 2 times (10s) |
||
Power consumption |
<0.6VA (each phase) |
||
Impedance |
>200kΩ |
||
Current |
Rated current |
AC5A / AC1A |
|
Excess load |
Continuance: 1.2 times; Instantaneous: 10 times (5s) |
||
Power consumption |
<0.4VA (each phase) |
||
Impedance |
<20mΩ |
||
Frequency |
45-65Hz (?0.01Hz) |
||
Electric energy |
Bi-directional Active/Reactive electric energy metering |
||
Power supply |
Working scope |
AC/DC 85-264V |
|
Power consumption |
<5VA |
||
Function modules |
Electric energy pulse |
Passive optical coupler collector output |
|
Communication interface |
1-way RS485 communication interface, Modbus-RTU Protocol |
||
Transmission output |
0-20mA/4-20mA/0-5V/1-5V transmission output, programmable to setting transmission items and relative output data. |
||
Security |
Insulation resistance |
≥100MΩ |
|
Resist pressure |
Input voltage>1kV, Input and output>2kV, Power supply and output>2kV |
||
Work environment |
Temperature |
-10℃~55℃ |
|
Relative humidity |
≤93%RH |
||
Altitude |
Non-corrosive gas forum, Altitude ≤2500m |
||
storage environment |
Temperature |
-20℃~75℃ |
|
Relative humidity |
≤93%RH |
6. Outline Dimension
DC284H-2X1
DC284H-9X1
DC284H-1X1
7. Typical Signal Input Wiring Diagram
Note: the above diagram is only for reference, the actual parameters in the factory shall prevail.
8. Ordering Example
When order please specify the required models, power supply, signal input, the transformation ratio, display requirements and relative content. Accuracy class, the default is Class 0.5. For example, if need Class 0.2, please specify when ordering.
l Model: DC284H-2X1
l Power supply: AC 220V
l Signal Input: 2 Voltage 1current mode: 1A, AC5A; UAB, AC100V
l Other: other factory pre-sets (if no indication when ordering, ex-factory products will be delivered in accordance with the default setting).